Description
insulation resistance |
> 1 MOhm 500 V DC for 1 minute to earth
|
---|---|
noise level |
54.5 dB 86/188/EEC
|
power dissipation in W |
36 W natural convection 380 V 4 kHz
145 W forced convection 380 V 4 kHz |
volume of cooling air |
38 m3/h
|
operating position |
Vertical +/- 10 degree
|
THDI |
<= 48 % full load IEC 61000-3-12
|
electromagnetic compatibility |
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
1.2/50 µs – 8/20 µs surge immunity test level 3 IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 Electrostatic discharge immunity test level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 |
pollution degree |
2 EN/IEC 61800-5-1
|
vibration resistance |
1.5 mm peak to peak 2…13 Hz IEC 60068-2-6
1 gn 13…200 Hz IEC 60068-2-6 |
shock resistance |
15 gn 11 ms IEC 60068-2-27
|
relative humidity |
5…95 % without condensation IEC 60068-2-3
|
ambient air temperature for operation |
-15…50 °C without derating
50…60 °C with derating factor |
ambient air temperature for storage |
-40…70 °C
|
operating altitude |
1000…4800 m with current derating 1 % per 100 m
<= 1000 m without derating |
environmental characteristic |
Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
Dust pollution resistance class 3S3 EN/IEC 60721-3-3 |
standards |
EN/IEC 61800-3
EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 |