Opis
GV2-termo-magnetski-prekidaC 6…10 A-prikljuCci vijCanim stezaljkama
range |
TeSys
|
---|---|
product name |
TeSys GV2
|
device short name |
GV2ME
|
device application |
Motor
|
trip unit technology |
Thermal-magnetic
|
poles description |
3P
|
---|---|
network type |
AC
|
utilisation category |
AC-3 IEC 60947-4-1
Category A IEC 60947-2 |
network frequency |
50/60 Hz IEC 60947-4-1
|
fixing mode |
35 mm symmetrical DIN rail clipped
Panel screwed with adaptor plate) |
operating position |
Any position
|
motor power kW |
3 kW 400/415 V AC 50/60 Hz
4 kW 400/415 V AC 50/60 Hz 4 kW 500 V AC 50/60 Hz 5,5 kW 690 V AC 50/60 Hz 7,5 kW 690 V AC 50/60 Hz 5,5 kW 500 V AC 50/60 Hz |
breaking capacity |
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 15 kA Icu 440 V AC 50/60 Hz IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity |
100 % 500 V AC 50/60 Hz IEC 60947-2
100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 75 % 690 V AC 50/60 Hz IEC 60947-2 |
control type |
Push-button
|
[In] rated current |
10 A
|
thermal protection adjustment range |
6…10 A
|
magnetic tripping current |
138 A
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz IEC 60947-2
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz IEC 60947-2
|
[Ith] conventional free air thermal current |
10 A IEC 60947-4-1
|
[Uimp] rated impulse withstand voltage |
6 kV IEC 60947-2
|
power dissipation per pole |
2,5 W
|
mechanical durability |
100000 cycles
|
electrical durability |
100000 cycles AC-3 440 V
|
maximum operating rate |
25 cyc/h
|
rated duty |
Continuous IEC 60947-4-1
|
connections – terminals |
screw clamp terminals 2 1…6 mm² solid
screw clamp terminals 2 1,5…6 mm² flexible without cable end screw clamp terminals 2 1…4 mm² flexible with cable end |
tightening torque |
1,7 N.m screw clamp terminals
|
suitability for isolation |
Yes IEC 60947-1
|
phase failure sensitivity |
Yes IEC 60947-4-1
|
height |
89 mm
|
width |
45 mm
|
depth |
78,2 mm
|
net weight |
0,26 kg
|
GV2ME14