Opis
Sklopka
range |
TeSys
|
---|---|
product name |
TeSys D
|
product or component type |
Contactor
|
device short name |
LC1D
|
contactor application |
Resistive load
Motor control |
utilisation category |
AC-3
AC-4 AC-1 |
poles description |
3P
|
power pole contact composition |
3 NO
|
[Ue] rated operational voltage |
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
|
[Ie] rated operational current |
18 A 60 °C) <= 440 V AC AC-3 power circuit
32 A 60 °C) <= 440 V AC AC-1 power circuit
|
motor power kW |
4 kW 220…230 V AC 50/60 Hz AC-3)
7,5 kW 380…400 V AC 50/60 Hz AC-3) 9 kW 415…440 V AC 50/60 Hz AC-3) 10 kW 500 V AC 50/60 Hz AC-3) 10 kW 660…690 V AC 50/60 Hz AC-3) 4 kW 400 V AC 50/60 Hz AC-4) |
motor power HP (UL / CSA) |
1 hp 115 V AC 50/60 Hz 1 phase
3 hp 230/240 V AC 50/60 Hz 1 phase 5 hp 200/208 V AC 50/60 Hz 3 phases 5 hp 230/240 V AC 50/60 Hz 3 phases 10 hp 460/480 V AC 50/60 Hz 3 phases 15 hp 575/600 V AC 50/60 Hz 3 phases |
control circuit type |
AC 50/60 Hz
|
[Uc] control circuit voltage |
380 V AC 50/60 Hz
|
auxiliary contact composition |
1 NO + 1 NC
|
[Uimp] rated impulse withstand voltage |
6 kV IEC 60947
|
overvoltage category |
III
|
[Ith] conventional free air thermal current |
10 A 60 °C signalling circuit
32 A 60 °C power circuit |
Irms rated making capacity |
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1 300 A 440 V power circuit IEC 60947 |
rated breaking capacity |
300 A 440 V power circuit IEC 60947
|
[Icw] rated short-time withstand current |
145 A 40 °C – 10 s power circuit
240 A 40 °C – 1 s power circuit 40 A 40 °C – 10 min power circuit 84 A 40 °C – 1 min power circuit 100 A – 1 s signalling circuit 120 A – 500 ms signalling circuit 140 A – 100 ms signalling circuit |
associated fuse rating |
10 A gG signalling circuit IEC 60947-5-1
50 A gG <= 690 V type 1 power circuit 35 A gG <= 690 V type 2 power circuit |
average impedance |
2,5 mOhm – Ith 32 A 50 Hz power circuit
|
[Ui] rated insulation voltage |
Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
electrical durability |
1,65 Mcycles 18 A AC-3 <= 440 V
1 Mcycles 32 A AC-1 <= 440 V
|
power dissipation per pole |
2,5 W AC-1
0,8 W AC-3 |
safety cover |
With
|
mounting support |
Rail
Plate |
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
product certifications |
RINA
LROS (Lloyds register of shipping) GL CSA BV GOST DNV CCC UL |
connections – terminals |
Control circuit screw clamp terminals 1 1…4 mm²flexible without cable end
Control circuit screw clamp terminals 2 1…4 mm²flexible without cable end Control circuit screw clamp terminals 1 1…4 mm²flexible with cable end Control circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end Control circuit screw clamp terminals 1 1…4 mm²solid without cable end Control circuit screw clamp terminals 2 1…4 mm²solid without cable end Power circuit screw clamp terminals 1 1,5…6 mm²flexible without cable end Power circuit screw clamp terminals 2 1,5…6 mm²flexible without cable end Power circuit screw clamp terminals 1 1…6 mm²flexible with cable end Power circuit screw clamp terminals 2 1…4 mm²flexible with cable end Power circuit screw clamp terminals 1 1,5…6 mm²solid without cable end Power circuit screw clamp terminals 2 1,5…6 mm²solid without cable end |
tightening torque |
Power circuit 1,7 N.m screw clamp terminals flat Ø 6 mm
Power circuit 1,7 N.m screw clamp terminals Philips No 2 Control circuit 1,7 N.m screw clamp terminals flat Ø 6 mm Control circuit 1,7 N.m screw clamp terminals Philips No 2 |
operating time |
12…22 ms closing
4…19 ms opening |
safety reliability level |
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
mechanical durability |
15 Mcycles
|
maximum operating rate |
3600 cyc/h 60 °C
|
coil technology |
Without built-in suppressor module
|
---|---|
control circuit voltage limits |
Drop-out 0.3…0.6 Uc AC 50/60 Hz 60 °C)
Operational 0.8…1.1 Uc AC 50 Hz 60 °C) Operational 0.85…1.1 Uc AC 60 Hz 60 °C) |
inrush power in VA |
70 VA 60 Hz 0,75 20 °C)
70 VA 50 Hz 0,75 20 °C) |
hold-in power consumption in VA |
7,5 VA 60 Hz 0,3 20 °C)
7 VA 50 Hz 0,3 20 °C) |
heat dissipation |
2…3 W 50/60 Hz
|
auxiliary contacts type |
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1 |
signalling circuit frequency |
25…400 Hz
|
minimum switching current |
5 mA signalling circuit
|
minimum switching voltage |
17 V signalling circuit
|
non-overlap time |
1,5 ms on de-energisation between NC and NO contact
1,5 ms on energisation between NC and NO contact |
insulation resistance |
> 10 MOhm signalling circuit
|