Description
Modul relej
range of product |
Zelio Logic
|
---|---|
product or component type |
Modular smart relay
|
local display |
With
|
---|---|
number or control scheme lines |
0…500 with FBD programming
0…240 with ladder programming |
cycle time |
6…90 ms
|
backup time |
10 years at 25 °C
|
clock drift |
6 s/month at 25 °C
12 min/year at 0…55 °C |
checks |
Program memory on each power up
|
[Us] rated supply voltage |
24 V
|
supply voltage limits |
19.2…30 V
|
supply current |
160 mA (with extensions)
50 mA (without extension) |
power dissipation in W |
4 W without extension
8 W with extensions |
reverse polarity protection |
With
|
discrete input number |
6 conforming to EN/IEC 61131-2 type 1
|
discrete input type |
Resistive
|
discrete input voltage |
24 V DC
|
discrete input current |
4 mA
|
counting frequency |
1 kHzfor discrete input
|
voltage state 1 guaranteed |
>= 15 Vfor I1…IA and IH…IR discrete input circuit
>= 15 Vfor IB…IG used as discrete input circuit |
voltage state 0 guaranteed |
<= 5 Vfor I1...IA and IH...IR discrete input circuit
<= 5 Vfor IB...IG used as discrete input circuit
|
current state 1 guaranteed |
>= 1.2 mAfor IB…IG used as discrete input circuit
>= 2.2 mAfor I1…IA and IH…IR discrete input circuit |
current state 0 guaranteed |
<= 0.5 mAfor IB...IG used as discrete input circuit
<= 0.75 mAfor I1...IA and IH...IR discrete input circuit
|
input compatibility |
3-wire proximity sensors PNP (discrete input)
|
analogue input number |
4
|
analogue input type |
Common mode
|
analogue input range |
0…24 V
0…10 V |
maximum permissible voltage |
30 V (analogue input circuit)
|
analogue input resolution |
8 bits
|
LSB value |
39 mV (analogue input circuit)
|
conversion time |
Smart relay cycle timefor analogue input circuit
|
conversion error |
+/- 5 % at 25 °Cfor analogue input circuit
+/- 6.2 % at 55 °Cfor analogue input circuit |
repeat accuracy |
+/- 2 % at 55 °Cfor analogue input circuit
|
operating distance |
10 m between stations, with screened cable (sensor not isolated)for analogue input circuit
|
input impedance |
12 kOhm (IB…IG used as analogue input circuit)
12 kOhm (IB…IG used as discrete input circuit) 7.4 kOhm (I1…IA and IH…IR discrete input circuit) |
number of outputs |
4 transistor output(s)
|
output voltage |
24 V (transistor output)
|
output voltage limits |
19.2…30 V DC (transistor output)
|
load current |
0.5…0.625 A (transistor output)
|
[Ures] residual voltage |
<= 2 V at state 1 (transistor output)
|
overload protection |
With, transistor output
|
short-circuit protection |
With transistor output
|
overvoltage protection |
With, transistor output
|
clock |
With
|
response time |
<= 1 ms (from state 0 to state 1)for transistor output
<= 1 ms (from state 1 to state 0)for transistor output
|
connections – terminals |
Screw terminals, clamping capacity: 1 x 0.2…1 x 2.5 mm² AWG 25…AWG 14 semi-solid
Screw terminals, clamping capacity: 1 x 0.2…1 x 2.5 mm² AWG 25…AWG 14 solid Screw terminals, clamping capacity: 1 x 0.25…1 x 2.5 mm² AWG 24…AWG 14 flexible with cable end Screw terminals, clamping capacity: 2 x 0.2…2 x 1.5 mm² AWG 24…AWG 16 solid Screw terminals, clamping capacity: 2 x 0.25…2 x 0.75 mm² AWG 24…AWG 18 flexible with cable end |
tightening torque |
0.5 N.m
|
overvoltage category |
III conforming to EN/IEC 60664-1
|
product weight |
0.22 kg
|
immunity to microbreaks |
<= 1 ms
|
---|---|
product certifications |
C-Tick
CSA GL UL GOST |
standards |
EN/IEC 61000-4-3
EN/IEC 61000-4-4 level 3 EN/IEC 60068-2-27 Ea EN/IEC 61000-4-6 level 3 EN/IEC 61000-4-11 EN/IEC 61000-4-5 EN/IEC 61000-4-12 EN/IEC 61000-4-2 level 3 EN/IEC 60068-2-6 Fc |
IP degree of protection |
IP20 (terminal block) conforming to IEC 60529
IP40 (front panel) conforming to IEC 60529 |
environmental characteristic |
EMC directive conforming to EN/IEC 61000-6-2
EMC directive conforming to EN/IEC 61000-6-3 EMC directive conforming to EN/IEC 61000-6-4 EMC directive conforming to EN/IEC 61131-2 zone B Low voltage directive conforming to EN/IEC 61131-2 |
disturbance radiated/conducted |
Class B conforming to EN 55022-11 group 1
|
pollution degree |
2 conforming to EN/IEC 61131-2
|
ambient air temperature for operation |
-20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2
-20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
ambient air temperature for storage |
-40…70 °C
|
operating altitude |
2000 m
|
altitude transport |
<= 3048 m
|
relative humidity |
95 % without condensation or dripping water
|
[accordion-item title=”Original kataloÅ¡ki broj”]
SR3B102BD
[/accordion-item]
[accordion-item title=”Robna marka”]
Schneider
[/accordion-item]
[/accordion]