Opis
Sklopka-D-3P (3 NO)-AC-3-<= 440 V 50 A-zavojnica 230 V AC-50/60 Hz
range |
TeSys
|
---|---|
product name |
TeSys D
|
product or component type |
Contactor
|
device short name |
LC1D
|
contactor application |
Motor control
Resistive load |
utilisation category |
AC-1
AC-4 AC-3 |
poles description |
3P
|
power pole contact composition |
3 NO
|
[Ue] rated operational voltage |
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
|
[Ie] rated operational current |
50 A 60 °C) <= 440 V AC AC-3 power circuit
80 A 60 °C) <= 440 V AC AC-1 power circuit
|
motor power kW |
15 kW 220…230 V AC 50/60 Hz AC-3)
22 kW 380…400 V AC 50/60 Hz AC-3) 30 kW 500 V AC 50/60 Hz AC-3) 33 kW 660…690 V AC 50/60 Hz AC-3) 25 kW 415 V AC 50/60 Hz AC-3) 30 kW 440 V AC 50/60 Hz AC-3) 11 kW 400 V AC 50/60 Hz AC-4) |
motor power HP (UL / CSA) |
3 hp 115 V AC 50/60 Hz 1 phase
7,5 hp 230/240 V AC 50/60 Hz 1 phase 15 hp 200/208 V AC 50/60 Hz 3 phases 15 hp 230/240 V AC 50/60 Hz 3 phases 40 hp 460/480 V AC 50/60 Hz 3 phases 40 hp 575/600 V AC 50/60 Hz 3 phases |
control circuit type |
AC 50/60 Hz
|
[Uc] control circuit voltage |
230 V AC 50/60 Hz
|
auxiliary contact composition |
1 NO + 1 NC
|
[Uimp] rated impulse withstand voltage |
6 kV IEC 60947
|
overvoltage category |
III
|
[Ith] conventional free air thermal current |
10 A 60 °C signalling circuit
80 A 60 °C power circuit |
Irms rated making capacity |
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1 900 A 440 V power circuit IEC 60947 |
rated breaking capacity |
900 A 440 V power circuit IEC 60947
|
[Icw] rated short-time withstand current |
400 A 40 °C – 10 s power circuit
810 A 40 °C – 1 s power circuit 84 A 40 °C – 10 min power circuit 208 A 40 °C – 1 min power circuit 100 A – 1 s signalling circuit 120 A – 500 ms signalling circuit 140 A – 100 ms signalling circuit |
associated fuse rating |
10 A gG signalling circuit IEC 60947-5-1
100 A gG <= 690 V type 1 power circuit 100 A gG <= 690 V type 2 power circuit |
average impedance |
1,5 mOhm – Ith 80 A 50 Hz power circuit
|
[Ui] rated insulation voltage |
Power circuit 600 V CSA
Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL Power circuit 690 V IEC 60947-4-1 |
electrical durability |
1,45 Mcycles 50 A AC-3 <= 440 V
1,1 Mcycles 80 A AC-1 <= 440 V
|
power dissipation per pole |
3,7 W AC-3
9,6 W AC-1 |
safety cover |
With
|
mounting support |
Plate
Rail |
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
product certifications |
GL
BV GOST CCC CSA UL RINA LROS (Lloyds register of shipping) DNV |
connections – terminals |
Control circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…4 mm²flexible without cable end Control circuit screw clamp terminals 2 1…4 mm²flexible without cable end Control circuit screw clamp terminals 1 1…4 mm²flexible with cable end Control circuit screw clamp terminals 1 1…4 mm²solid without cable end Control circuit screw clamp terminals 2 1…4 mm²solid without cable end Power circuit screw connection 1 1…35 mm²flexible without cable end Power circuit screw connection 2 1…25 mm²flexible without cable end Power circuit screw connection 1 1…35 mm²flexible with cable end Power circuit screw connection 2 1…25 mm²flexible with cable end Power circuit screw connection 1 1…35 mm²solid without cable end Power circuit screw connection 2 1…25 mm²solid without cable end |
tightening torque |
Control circuit 1,7 N.m screw clamp terminals flat Ø 6 mm
Control circuit 1,7 N.m screw clamp terminals Philips No 2 Power circuit 8 N.m EverLink BTR screw connectors 25…35 mm² hexagonal 4 mm Power circuit 5 N.m EverLink BTR screw connectors 1…25 mm² hexagonal 4 mm |
operating time |
4…19 ms opening
12…26 ms closing |
safety reliability level |
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
mechanical durability |
6 Mcycles
|
maximum operating rate |
3600 cyc/h 60 °C
|
coil technology |
Without built-in suppressor module
|
---|---|
control circuit voltage limits |
Drop-out 0.3…0.6 Uc AC 50/60 Hz 60 °C)
Operational 0.8…1.1 Uc AC 50 Hz 60 °C) Operational 0.85…1.1 Uc AC 60 Hz 60 °C) |
inrush power in VA |
140 VA 60 Hz 0,75 20 °C)
160 VA 50 Hz 0,75 20 °C) |
hold-in power consumption in VA |
13 VA 60 Hz 0,3 20 °C)
15 VA 50 Hz 0,3 20 °C) |
heat dissipation |
4…5 W 50/60 Hz
|
auxiliary contacts type |
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1 |
signalling circuit frequency |
25…400 Hz
|
minimum switching current |
5 mA signalling circuit
|
minimum switching voltage |
17 V signalling circuit
|
non-overlap time |
1,5 ms on de-energisation between NC and NO contact
1,5 ms on energisation between NC and NO contact |
insulation resistance |
> 10 MOhm signalling circuit
|
IP degree of protection |
IP20 front face IEC 60529
|
---|---|
protective treatment |
TH IEC 60068-2-30
|
pollution degree |
3
|
ambient air temperature for operation |
-5…60 °C
|
ambient air temperature for storage |
-60…80 °C
|
permissible ambient air temperature around the device |
-40…70 °C at Uc
|
operating altitude |
3000 m without
|
fire resistance |
850 °C IEC 60695-2-1
|
flame retardance |
V1 UL 94
|
mechanical robustness |
Vibrations contactor open2 Gn, 5…300 Hz
Vibrations contactor closed4 Gn, 5…300 Hz Shocks contactor closed15 Gn for 11 ms Shocks contactor open10 Gn for 11 ms |
height |
122 mm
|
width |
55 mm
|
depth |
120 mm
|
net weight |
0,855 kg
|
-
Offer Sustainability Status održive ponude Proizvod Green PremiumUredba REACh Direktiva EU RoHS Proaktivna sukladnost (proizvod izvan zakonskog okvira direktive EU RoHS)
Izjava EU RoHSBez otrovnih teÅ¡kih metala DaBez žive DaInformacije o RoHS izuzeću Propis RoHS za Kinu Izjava o oÄ?uvanju okoliÅ¡a Profil cirkularnosti WEEE Proizvod se na tržiÅ¡tima EU mora odlagati u skladu sa specifiÄ?nim propisima o prikupljanju otpada; nikako se ne smije odlagati s komunalnim otpadom.Contractual warranty Jamstvo 18 months -
Dokumenti i preuzimanja
Jezik- hrvatski
- Latvian
- Danish
- Ukrainian
- French
- Finnish
- Chinese
- Hungarian
- Korean
- Russian
- Lithuanian
- Czech
- Italian
- Slovak
- Spanish
- Slovenian
- Serbian
- English
- Dutch
- Norwegian
- Turkish
- Kazakh
- Portuguese
- Macedonian
- Greek
- Polish
- Romanian
- German
- Swedish
- Bulgarian
- Estonian
KataloziDatum
VeliÄ?inaDodaj u Moje dokumenteTeSys catalogue – 2019 – 2020 – chapter B8 contactors TeSys SK,K, D, SKGC, GC, GY,GF (Verzija 7.0)TeSys catalogue – 2019 – 2020 – chapter A2 – open, pre-cabled motor starters (Verzija 6.0)Tesys catalogue 2019 – 2020 Motor control and protection components (Verzija 9.2)Control Panel Technical Guide – How to quickly design optimized contactor assemblies (Verzija 1.1)CADCAD file (on TraceParts) for LC1D50AP7: TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 50 A - 230 V AC 50/60 Hz coil (Verzija 2.0)CAD for LC1D50AP7: TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 50 A - 230 V AC 50/60 Hz coil (Verzija 1.0)3P EVLK CONT 40A 18,5KW (Verzija 1.0)