Opis
product weight |
0.116 kg
|
---|---|
resistance to high pressure washer |
7000000 Pa at 55 °C,distance: 0.1 m
|
colour of marking |
Black marking when white caps
White marking when green, red or black caps |
operator profile |
Green flush, white I
Red projecting, white O |
contacts usage |
Standard contacts
|
positive opening |
With positive opening conforming to EN/IEC 60947-5-1 appendix K
|
operating travel |
1.5 mm (NC changing electrical state)
2.6 mm (NO changing electrical state) 4.3 mm (total travel) |
operating force |
3.5 N (NC changing electrical state)
3.8 N (NO changing electrical state) |
mechanical durability |
1000000 cycles
|
tightening torque |
0.8…1.2 N.m conforming to EN 60947-1
|
shape of screw head |
Cross head compatible with JIS No 1 screwdriver
Cross head compatible with Philips no 1 screwdriver Cross head compatible with pozidriv No 1 screwdriver Slotted head compatible with flat Ø 4 mm screwdriver Slotted head compatible with flat Ø 5.5 mm screwdriver |
contacts material |
Silver alloy (Ag/Ni)
|
short-circuit protection |
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
|
[Ith] conventional free air thermal current |
10 A conforming to EN/IEC 60947-5-1
|
[Ui] rated insulation voltage |
600 V (degree of pollution: 3) conforming to EN 60947-1
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-1
|
[Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1 |
electrical durability |
1000000 cycles, AC-15, 2 A at 230 V, operating rate: 3600 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1
1000000 cycles, AC-15, 3 A at 120 V, operating rate: 3600 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 1000000 cycles, AC-15, 4 A at 24 V, operating rate: 3600 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate: 3600 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate: 3600 cyc/mn, load factor: 0.5 conforming to EN/IEC 60947-5-1 |
electrical reliability |
? < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4
? < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4 |