Description
Sklopka-contakter 3P-440V-95A-zavojnica 230V AC-50/60Hz
range |
TeSys
|
---|---|
product name |
TeSys D
|
product or component type |
Contactor
|
device short name |
LC1D
|
contactor application |
Resistive load
Motor control |
utilisation category |
AC-1
AC-3 AC-4 |
poles description |
3P
|
power pole contact composition |
3 NO
|
[Ue] rated operational voltage |
Power circuit <= 300 V DC 25...400 Hz
Power circuit <= 1000 V AC
|
[Ie] rated operational current |
125 A 60 °C) <= 440 V AC AC-1 power circuit
95 A 60 °C) <= 440 V AC AC-3 power circuit
|
motor power kW |
45 kW 415…440 V AC 50/60 Hz AC-3)
55 kW 500 V AC 50/60 Hz AC-3) 45 kW 660…690 V AC 50/60 Hz AC-3) 45 kW 1000 V AC 50/60 Hz AC-3) 15 kW 400 V AC 50/60 Hz AC-4) 25 kW 220…230 V AC 50/60 Hz AC-3) 45 kW 380…400 V AC 50/60 Hz AC-3) |
motor power HP (UL / CSA) |
20 hp 200/208 V AC 50/60 Hz 3 phases
7,5 hp 115 V AC 50/60 Hz 1 phase 15 hp 230/240 V AC 50/60 Hz 1 phase 25 hp 230/240 V AC 50/60 Hz 3 phases 60 hp 460/480 V AC 50/60 Hz 3 phases 60 hp 575/600 V AC 50/60 Hz 3 phases |
control circuit type |
AC 50/60 Hz
|
[Uc] control circuit voltage |
230 V AC 50/60 Hz
|
auxiliary contact composition |
1 NO + 1 NC
|
[Uimp] rated impulse withstand voltage |
8 kV IEC 60947
|
overvoltage category |
III
|
[Ith] conventional free air thermal current |
10 A 60 °C signalling circuit
125 A 60 °C power circuit |
Irms rated making capacity |
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1 1100 A 440 V power circuit IEC 60947 |
rated breaking capacity |
1100 A 440 V power circuit IEC 60947
|
[Icw] rated short-time withstand current |
1100 A 40 °C – 1 s power circuit
135 A 40 °C – 10 min power circuit 800 A 40 °C – 10 s power circuit 400 A 40 °C – 1 min power circuit 100 A – 1 s signalling circuit 120 A – 500 ms signalling circuit 140 A – 100 ms signalling circuit |
associated fuse rating |
10 A gG signalling circuit IEC 60947-5-1
200 A gG <= 690 V type 1 power circuit 160 A gG <= 690 V type 2 power circuit |
average impedance |
0,8 mOhm – Ith 125 A 50 Hz power circuit
|
[Ui] rated insulation voltage |
Power circuit 600 V CSA
Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
electrical durability |
1,2 Mcycles 95 A AC-3 <= 440 V
1,3 Mcycles 125 A AC-1 <= 440 V
|
power dissipation per pole |
12,5 W AC-1
7,2 W AC-3 |
safety cover |
With
|
mounting support |
Plate
Rail |
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
product certifications |
LROS (Lloyds register of shipping)
DNV GOST RINA CCC BV GL |
connections – terminals |
Control circuit screw clamp terminals 2 1…2,5 mm²flexible with cable end
Control circuit screw clamp terminals 1 1…2,5 mm²flexible with cable end Control circuit screw clamp terminals 1 1…4 mm²flexible without cable end Control circuit screw clamp terminals 2 1…4 mm²flexible without cable end Control circuit screw clamp terminals 1 1…4 mm²solid without cable end Control circuit screw clamp terminals 2 1…4 mm²solid without cable end Power circuit connector 1 4…50 mm²flexible without cable end Power circuit connector 2 4…25 mm²flexible without cable end Power circuit connector 1 4…50 mm²flexible with cable end Power circuit connector 2 4…16 mm²flexible with cable end Power circuit connector 1 4…50 mm²solid without cable end Power circuit connector 2 4…25 mm²solid without cable end |
tightening torque |
Control circuit 1,2 N.m screw clamp terminals flat Ø 6 mm
Control circuit 1,2 N.m screw clamp terminals Philips No 2 Power circuit 9 N.m connector flat Ø 6 to Ø 8 mm Power circuit 9 N.m connector hexagonal 4 mm |
operating time |
20…35 ms closing
6…20 ms opening |
safety reliability level |
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
mechanical durability |
4 Mcycles
|
maximum operating rate |
3600 cyc/h 60 °C
|
coil technology |
Without built-in suppressor module
|
---|---|
control circuit voltage limits |
Operational 0.85…1.1 Uc AC 60 Hz 55 °C)
Drop-out 0.3…0.6 Uc AC 50/60 Hz 55 °C) Operational 0.8…1.1 Uc AC 50 Hz 55 °C) |
inrush power in VA |
245 VA 60 Hz 0,75 20 °C)
245 VA 50 Hz 0,75 20 °C) |
hold-in power consumption in VA |
26 VA 60 Hz 0,3 20 °C)
26 VA 50 Hz 0,3 20 °C) |
heat dissipation |
6…10 W 50/60 Hz
|
auxiliary contacts type |
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1 |
signalling circuit frequency |
25…400 Hz
|
minimum switching current |
5 mA signalling circuit
|
minimum switching voltage |
17 V signalling circuit
|
non-overlap time |
1,5 ms on de-energisation between NC and NO contact
1,5 ms on energisation between NC and NO contact |
insulation resistance |
> 10 MOhm signalling circuit
|
IP degree of protection |
IP20 front face IEC 60529
|
---|---|
protective treatment |
TH IEC 60068-2-30
|
pollution degree |
3
|
ambient air temperature for operation |
-5…60 °C
|
ambient air temperature for storage |
-60…80 °C
|
permissible ambient air temperature around the device |
-40…70 °C at Uc
|
operating altitude |
3000 m without
|
fire resistance |
850 °C IEC 60695-2-1
|
flame retardance |
V1 UL 94
|
mechanical robustness |
Vibrations contactor open2 Gn, 5…300 Hz
Shocks contactor open8 Gn for 11 ms Vibrations contactor closed3 Gn, 5…300 Hz Shocks contactor closed10 Gn for 11 ms |
height |
127 mm
|
width |
85 mm
|
depth |
130 mm
|
net weight |
1,61 kg
|
[accordion-item title=”Original kataloÅ¡ki broj”]
LC1D95P7
[/accordion-item]
[accordion-item title=”Robna marka”]
SCHNEIDER
[/accordion-item]
[/accordion]