Description
Pomo?ni kontaktni blok-1 NO + 3 NC-prikljuCci vijCane stezaljke za seriju LC1D
range of product |
TeSys D
TeSys F TeSys D control relay |
---|---|
range |
TeSys
|
device short name |
LADN
|
product or component type |
Auxiliary contact block
|
range compatibility |
TeSys D CR1F contactor
|
auxiliary contacts operation |
Instantaneous
|
pole contact composition |
1 NO + 3 NC
|
connections – terminals |
screw clamp terminals 1 1…2,5 mm²flexible with cable end
screw clamp terminals 1 1…2,5 mm²flexible without cable end screw clamp terminals 2 1…2,5 mm²flexible with cable end screw clamp terminals 2 1…2,5 mm²flexible without cable end screw clamp terminals 1 1…2,5 mm²solid with cable end screw clamp terminals 1 1…2,5 mm²solid without cable end screw clamp terminals 2 1…2,5 mm²solid with cable end screw clamp terminals 2 1…2,5 mm²solid without cable end |
mounting location |
Front
|
---|---|
[Ui] rated insulation voltage |
600 V UL
690 V IEC 60947-5-1 600 V CSA |
[Ue] rated operational voltage |
690 V AC 25…400 Hz
|
[Ith] conventional free air thermal current |
10 A 60 °C
|
Irms rated making capacity |
140 A <= 690 V AC IEC 60947-5-1
250 A <= 690 V DC IEC 60947-5-1
|
permissible short-time rating |
100 A 60 °C 1 s
120 A 60 °C 500 ms 140 A 60 °C 100 ms |
protection type |
GG fuse 10 A rating according to operational current for Ue <= 690 V
|
associated fuse rating |
10 A gG IEC 60947-5-1
|
mechanical durability |
30 Mcycles
|
minimum switching current |
5 mA
|
minimum switching voltage |
17 V
|
non-overlap time |
1,5 ms on de-energisation no overlap between NC and NO contact
1,5 ms on energisation no overlap between NC and NO contact |
overlap time |
1,5 ms
|
insulation resistance |
> 10 MOhm
|
net weight |
0,05 kg
|
LADN13
SCHNEIDER