Opis
Sklopka
range |
TeSys
|
---|---|
product name |
TeSys D
|
product or component type |
Contactor
|
device short name |
LC1D
|
contactor application |
Resistive load
Motor control |
utilisation category |
AC-3
AC-1 AC-4 |
poles description |
3P
|
power pole contact composition |
3 NO
|
[Ue] rated operational voltage |
<= 300 V DCfor power circuit
<= 690 V AC 25...400 Hz for power circuit
|
[Ie] rated operational current |
40 A (<= 60 °C) at <= 440 V AC AC-3for power circuit
60 A (<= 60 °C) at <= 440 V AC AC-1for power circuit
|
motor power kW |
18.5 kW at 380…400 V AC 50/60 Hz AC-3
22 kW at 500 V AC 50/60 Hz AC-3 30 kW at 660…690 V AC 50/60 Hz AC-3 11 kW at 220…230 V AC 50/60 Hz AC-3 9 kW at 400 V AC 50/60 Hz AC-4 22 kW at 415…440 V AC 50/60 Hz AC-3 |
motor power HP (UL / CSA) |
5 hp at 230/240 V AC 50/60 Hzfor 1 phase motors
10 hp at 230/240 V AC 50/60 Hzfor 3 phases motors 30 hp at 575/600 V AC 50/60 Hzfor 3 phases motors 3 hp at 115 V AC 50/60 Hzfor 1 phase motors 10 hp at 200/208 V AC 50/60 Hzfor 3 phases motors 30 hp at 460/480 V AC 50/60 Hz for 3 phases motors |
control circuit type |
AC 50/60 Hz
|
[Uc] control circuit voltage |
230 V AC 50/60 Hz
|
auxiliary contact composition |
1 NO + 1 NC
|
[Uimp] rated impulse withstand voltage |
Conforming to IEC 60947
|
overvoltage category |
III
|
[Ith] conventional free air thermal current |
60 A at <= 60 °C for power circuit
10 A at <= 60 °Cfor signalling circuit
|
Irms rated making capacity |
800 A at 440 V for power circuit conforming to IEC 60947
140 A ACfor signalling circuit conforming to IEC 60947-5-1 250 A DCfor signalling circuit conforming to IEC 60947-5-1 |
rated breaking capacity |
800 A at 440 V for power circuit conforming to IEC 60947
|
[Icw] rated short-time withstand current |
100 A 1 s signalling circuit
120 A 500 ms signalling circuit 140 A 100 ms signalling circuit 320 A <= 40 °C 10 s power circuit 720 A <= 40 °C 1 s power circuit 72 A <= 40 °C 10 min power circuit 165 A <= 40 °C 1 min power circuit |
associated fuse rating |
80 A gG at <= 690 V coordination type 1 for power circuit
80 A gG at <= 690 V coordination type 2 for power circuit
10 A gGfor signalling circuit conforming to IEC 60947-5-1
|
average impedance |
1.5 mOhm at 50 Hz – Ith 60 Afor power circuit
|
[Ui] rated insulation voltage |
600 V for power circuit certifications CSA
600 V for power circuit certifications UL 690 V for power circuit conforming to IEC 60947-4-1 690 Vfor signalling circuit conforming to IEC 60947-1 600 Vfor signalling circuit certifications CSA 600 Vfor signalling circuit certifications UL |
electrical durability |
1.5 Mcycles 40 A AC-3 at Ue <= 440 V
1.4 Mcycles 60 A AC-1 at Ue <= 440 V
|
power dissipation per pole |
5.4 W AC-1
2.4 W AC-3 |
safety cover |
With
|
mounting support |
Plate
Rail |
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
product certifications |
UL
CCC GOST CSA |
connections – terminals |
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² – cable stiffness: flexible – with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: solid – without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: solid – without cable end Power circuit: screw connection 2 cable(s) 1…25 mm² – cable stiffness: flexible – with cable end Power circuit: screw connection 2 cable(s) 1…25 mm² – cable stiffness: solid – without cable end Power circuit: screw connection 2 cable(s) 1…25 mm² – cable stiffness: flexible – without cable end Power circuit: screw connection 1 cable(s) 1…35 mm² – cable stiffness: solid – without cable end Power circuit: screw connection 1 cable(s) 1…35 mm² – cable stiffness: flexible – without cable end Power circuit: screw connection 1 cable(s) 1…35 mm² – cable stiffness: flexible – with cable end |
tightening torque |
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal 4 mm Power circuit: 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal 4 mm |
operating time |
12…26 ms closing
4…19 ms opening |
safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
mechanical durability |
6 Mcycles
|
operating rate |
<= 3600 cyc/h at <= 60 °C
|
coil technology |
Without built-in suppressor module
|
---|---|
control circuit voltage limits |
0.3…0.6 Uc drop-out at 60 °C, AC 50/60 Hz
0.8…1.1 Uc operational at 60 °C, AC 50 Hz 0.85…1.1 Uc operational at 60 °C, AC 60 Hz |
inrush power in VA |
140 VA at 20 °C (cos Ï• 0.75) 60 Hz
160 VA at 20 °C (cos Ï• 0.75) 50 Hz |
hold-in power consumption in VA |
13 VA at 20 °C (cos Ï• 0.3) 60 Hz
15 VA at 20 °C (cos Ï• 0.3) 50 Hz |
heat dissipation |
4…5 W at 50/60 Hz
|
auxiliary contacts type |
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1 |
signalling circuit frequency |
25…400 Hz
|
minimum switching current |
5 mAfor signalling circuit
|
minimum switching voltage |
17 Vfor signalling circuit
|
non-overlap time |
1.5 ms on de-energisation (between NC and NO contact)
1.5 ms on energisation (between NC and NO contact) |
insulation resistance |
> 10 MOhmfor signalling circuit
|
IP degree of protection |
IP20 front face conforming to IEC 60529
|
---|---|
protective treatment |
TH conforming to IEC 60068-2-30
|
pollution degree |
3
|
ambient air temperature for operation |
-5…60 °C
|
ambient air temperature for storage |
-60…80 °C
|
permissible ambient air temperature around the device |
-40…70 °C at Uc
|
operating altitude |
3000 m without derating
|
fire resistance |
850 °C conforming to IEC 60695-2-1
|
flame retardance |
V1 conforming to UL 94
|
mechanical robustness |
Vibrations contactor open 2 Gn, 5…300 Hz
Vibrations contactor closed 4 Gn, 5…300 Hz Shocks contactor open 10 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms |
height |
122 mm
|
width |
55 mm
|
depth |
120 mm
|
product weight |
0.85 kg
|
[accordion-item title=”Original kataloÅ¡ki broj”]
LC1D40AP7
[/accordion-item]
[accordion-item title=”Robna marka”]
SCHNEIDER
[/accordion-item]
[/accordion]